THANK-YOU FOR SHARING THIS PAGE

HVAC Safety Recall Alerts
Keep you and your customers/clients up to date.  Copy and Paste the below code to place our “recall” logo and page link on your website or blog.

HVAC Recalls
2000 – Present

This listing has been assembled as a quick reference guide primarily for commercial and residential building inspectors.  If you’re aware of additional recalls that should be addressed, please email us.

This list  is by no means complete. Please visit the CPSC Website @ www.cpsc.gov/Recalls for other listings not included here.  (Recalls prior to 2000 are not included in this listing…simply because most of those units are near or have reached their expected useful life (EUL).
ADP – FOA Series Unit Heaters – CPSC Recall #11-198 (Apr. – 2011)
Description and Models:

This recall involves ADP FOA series unit heaters with heating capacity, model and serial numbers listed below. These unit heaters are separated combustion and gas-fired. The brand name “ADP”, the model number and the serial number can be found on the nameplate located inside the control cabinet.

Heating Capacity Model Number Serial Number Range

60,000 BTUH FOAN-60-1-1-1 5609K#### to 5610M#####

100,000 BTUH FOAN-100-1-1-1 6003J#### to 6010L##### and
5603J#### to 5610L#####

100,000 BTUH FOAP-100-1-1-1 6003J#### to 6010L##### and
5603J#### to 5610L#####

125,000 BTUH FOAN-125-1-1-1 6003J#### to 6010L##### and
5603J#### to 5610L#####

125,000 BTUH FOAP-125-1-1-1 6003J#### to 6010L##### and
5603J#### to 5610L#####

Remedy:

Consumers should stop using these recalled heaters immediately. Consumers should contact ADP to schedule an inspection and, if necessary, repair of the heater.
Incidents/Injuries:

None reported.
Sold At:

ADP dealers and distributors nationwide from September 2003 through April 2011 for between $2,700 and $4,200.
Manufacturer(s):
Lennox Industries Inc., of Richardson, Texas or Advanced Distributor Products (ADP) LLC, of Grenada, Miss.
Distributor(s):

Advanced Distributor Products (ADP) LLC, of Grenada, Miss.

View Recall

ADP FOA series and Lennox unit heater recall

ADP FOA series and Lennox unit heater recall

ADP FOA series and Lennox unit heater data tag.

ADP FOA series and Lennox unit heater Data Tag

Amana – AMEH80 Series Furnaces – CPSC Recall #17-145 (May. – 2017)
Description:
This recall involves 80% efficiency gas-fired furnaces sold under the Goodman, Amana and Daikin brand names used with home heating and cooling systems. The recalled products have model numbers beginning AMEH80, DM80HE, and GME8, and serial numbers beginning 1609, 1610, 1611 and 1612. The brand name is shown on the outside of the furnace, and the serial number is located on the label found by opening the furnace door.
View Recall

Amana AMEH80 furnace

Amana AMEH80 furnace

Amana AMEH80 furnace data tag with model and serial number would be similar to this Goodman tag.

Goodman Brand Furnace Data Tag

Amana – Packaged Terminal Air Conditioner/Heat Pump (PTAC) units – CPSC Recall #14-263 (Aug. – 2014)
Description:
This recall involves Amana, Century, Comfort-Aire, Goodman and York International-branded Packaged Terminal Air Conditioners and Heat Pumps. The units are rated 230/208 volt, 3.5 kW and are most often installed in walls of hotels, motels, apartment buildings and commercial spaces to provide room climate control. The recalled units are beige with serial numbers ranging from 0701009633 through 0804272329. The brand name is located on the unit’s front cover. The serial number is located on the control board plate found by lifting the unit’s front cover.
View Recall

Amana, Century, Comfort-Aire, Goodman and York International Packaged Terminal Air Conditioner/Heat Pump (PTAC)

Amana, Century, Comfort-Aire, Goodman and York International Packaged Terminal Air Conditioner/Heat Pump (PTAC)

American Standard – Furnaces – CPSC Recall #17-709 (Nov. – 2016)
Description:
This recall involves Trane, American Standard, Ameristar brand or unbranded furnaces. The recalled furnaces include serial numbers beginning with 16304 through 16324. The model and serial numbers are printed on a white label on the left or right-hand side of the unit. The following model numbers are included in the recall:  (See Recall for complete list).

View Recall

American Standard furnace

American Standard Brands

American Standard furnace data tag with model and serial number

American Standard Brands Data Tag

American Standard – Silver SI Outdoor Unit Air Conditioner – CPSC Recall #14-737 (Jun. – 2014)
Description:
This recall involves 37 models of Trane XB300 and American Standard brand Silver SI split system outdoor cooling units. The units are gray and have a black grated front. The units were sold in two sizes: 25.5 inches deep by 23.5 inches wide by 28.83 inches tall and 28.83 inches deep by 28.48 inches wide by 29.28 inches tall. The Trane or American Standard logo is affixed to the front and model numbers are printed on the silver nameplate on the back of the unit. Models included in the recall are::  (See Recall for complete list).
View Recall

American Standard SI Outdoor Unit Air Conditioner

American Standard Brands

Ameristar – Furnaces – CPSC Recall #17-709 (Nov. – 2016)
Description:

This recall involves Trane, American Standard, Ameristar brand or unbranded furnaces. The recalled furnaces include serial numbers beginning with 16304 through 16324. The model and serial numbers are printed on a white label on the left or right-hand side of the unit. The following model numbers are included in the recall:  (See Recall for complete list).

View Recall

Ameristar furnace

Ameristar Brands

Ameristar furnace data tag with model and serial number

Ameristar Brands Data Tag

Bryant – Evolution Extreme™ Heat Pumps – CPSC Recall #17-150 (May 2017)
Description: This recall involves 2, 3, 4, and 5 ton size heat pump units sold under the Carrier Greenspeed and Bryant Evolution Extreme brand names. The units are used for cooling and heating homes. The Carrier Greenspeed model numbers are: 25VNA024, 25VNA036, 25VNA048, and 25VNA060. The Bryant Evolution Extreme model numbers are: 280ANV024, 280ANV036, 280ANV048, and 280ANV060. The model number can be found on the unit nameplate (or rating plate) located on one side of the unit’s exterior. On the Bryant unit, there is a label on top of the unit that reads “Bryant Evolution System.” View Recall

Bryant Evolution™ Extreme

Mountain View

Bryant – Packaged Terminal Air Conditioners (PTAC) and Heat Pumps (PTHP) – (Expanded Recall Feb. – 2017)
Description:
This expanded recall involves Packaged Terminal Air Conditioners (PTAC) and Packaged Terminal Heat Pumps (PTHP) sold under the Bryant, Carrier and Fast brand names. Recalled units include those with original power cords and those that received a replacement power cord as part of the 2007 recall.
The recalled units have capacities of 7,000; 9,000; 12,000 and 15,000 BTUs and plug into 208/230 volt outlets. The following brands and eight models are being recalled:
• Carrier models 52CE, 52CQ, 52PE, 52PQ, 52PC, 52ME, 52MQ;
• Bryant models 840, 841, and 842; and
• Fast models 840, 841, and 842.
Model and serial numbers are located on the ratings/data plate on the right front of the unit, underneath the removable front panel.  A complete list of the serial numbers involved in this recall is available by calling Carrier (800.761.8492).
View Recall

Bryant-Carrier-Fast Packaged Terminal Air Conditioners (PTAC) and Packaged Terminal Heat Pumps (PTHP)

Carrier Brands

Bryant- BW1 & BW2 Series gas-fired boilers – CPSC Recall #02-152 (May. – 2002)
The recalled boilers have the Dunkirk, Sears Kenmore, Bryant, Carrier, Payne, Lennox and Pennco brand names, which is written on the front of the boilers. The model and serial number are located on the data plate located on the right side of the boiler. The following models and serial numbers are included in the recall:

Brand Model Numbers Serial Numbers
Dunkirk/Sears Kenmore PVWB-4 through PVWB-9
PWB4 through PWB9
PWB-4 through PWB-9
PWX-4 through PWX-9
320100007S – 520100299S
010200098S – 090200182S
Lennox GWB8-105E through GWB8-280E
GWB8-105S through GWB8-280S
340100148S – 500100600S
010200199S – 050200279S
Carrier/Bryant/ Payne
BW1AAN000105 – BW1AAN000280
BW1AAP000105 – BW1AAP000280
BW2AAP000105 – BW2AAP000280
3601V04044S – 5201V08708S
0102V000015S – 0902V01118S
Pennco 1504HWID and 1509HWID(natural gas)
1504HWD and 1509HWD(natural gas)
1502HWID – 1509HWID (LPgas only)
1502HWD – 1509HWD (LP gas only)
90131-0924 through 90152-0424
90201-0421 through 90208-0424

Independent heating contractors sold and installed these boilers nationwide from August 2001 through March 2002 for between $1,200 and $3,000.

Consumers should contact ECR International immediately to arrange for a free repair. Consumers can call ECR International at (800) 241- 5501 between 8 a.m. and 5 p.m. ET Monday through Friday.

CPSC recommends that every home should have at least one CO alarm that meets the requirements of the most recent Underwriters Laboratories (UL) 2034 standard, International Approval Services 6-96 standard or the Canadian Standards Association 6.19-01 standard.

View Recall

Dunkirk/Sears Kenmore/Lennox/Carrier/Bryant/Payne/Pennco Boilers

Dunkirk/Sears Kenmore/Lennox/Carrier/Bryant/Payne/Pennco Boilers

Buderus – GB312 gas-fired, floor standing condensing boilers. – CPSC Recall #09-770 (Sep.. – 2009)
Hazard: A problem with the boiler’s ignition due to insufficient output voltage from the boiler’s transformer can damage the boiler’s venting. This can result in leaking flue gases, posing a risk of carbon monoxide poisoning to consumers.
Incidents/Injuries: No incidents or injuries reported in the United States. Two incidents were reported in Germany, neither of which resulted in injury.
Description: The recall involves the Buderus GB312 gas-fired, floor standing condensing boilers. Model numbers included in this recall are: 312/90, 312/120, 312/160, 312/200, 312/240 and 312/280. “BUDERUS GB312” is printed on the front of the boiler. The boilers are blue, approximately 60 inches high and between 39 and 55 inches wide.
Sold by: Plumbing and heating wholesale distributors to plumbing and heating contractors nationwide from April 2008 through February 2009 for between $12,000 and $24,000 installed.
Manufactured in: Germany
Remedy: Bosch has directly contacted consumers who purchased the recalled boilers, inspected and, if necessary, repaired the boilers.
View Recall

Buderus GB312 gas-fired Boiler Recall

Buderus Brands

Buderus GB312 gas-fired Boiler Recall Data Tag

Buderus Brands Data Tag

Buderus – GB142 gas-fired, wall-hung boilers. – CPSC Recall #09-752 (Jul.. – 2009)
The following product safety recall was voluntarily conducted by the firm in cooperation with the CPSC. Consumers should stop using recalled products immediately unless otherwise instructed. It is illegal to resell or attempt to resell a recalled consumer product.
Name of Product: Gas-Fired Wall-Hung Boilers
Units: About 90
Importers: Bosch Thermotechnology, of Londonderry, N.H.
Manufacturer: Nefit B.V. Inc., of the Netherlands
Hazard: An electrical connector can overheat, posing a fire hazard to consumers.
Incidents/Injuries: None reported.
Description: The recalled Buderus GB142 is a gas-fired, wall-hung boiler. The boilers are white and designed to be mounted on walls. The black control drawer in the bottom center of the front of the boiler is marked “Buderus GB 142.” Boilers with a green sticker inside the control drawer are not included. The model numbers included in the recall are 142/24, 142/30, 142/45 and 142/60. Only models with date codes of 7246 through 7256 are included in the recall. The model number and date code are located on a label on the bottom left side of the boiler.
Sold by: Wholesale distributors to plumbing and heating contractors nationwide from September 2007 through December 2007 for between $5,000 and $7,500.
Manufactured in: The Netherlands
Remedy: Consumers should stop using the recalled boilers immediately and contact their certified heating contractors or Bosch Thermotechnology for a free repair.
Consumer Contact: For additional information, call Bosch Thermotechnology at (800) 283-3787 between 9 a.m. and 5 p.m. ET Monday through Friday or visit the firm’s Web site at www.buderus.net
View Recall

Buderus GB142 gas-fired wall-hung Boiler Recall

Buderus Brands

Carrier – Greenspeed™ Heat Pumps – CPSC Recall #17-150 (May 2017)
Description: This recall involves 2, 3, 4, and 5 ton size heat pump units sold under the Carrier Greenspeed and Bryant Evolution Extreme brand names. The units are used for cooling and heating homes. The Carrier Greenspeed model numbers are: 25VNA024, 25VNA036, 25VNA048, and 25VNA060. The Bryant Evolution Extreme model numbers are: 280ANV024, 280ANV036, 280ANV048, and 280ANV060. The model number can be found on the unit nameplate (or rating plate) located on one side of the unit’s exterior. On the Bryant unit, there is a label on top of the unit that reads “Bryant Evolution System.” View Recall

Carrier Greenspeed™

Mountain View

Carrier – Packaged Terminal Air Conditioners (PTAC) and Heat Pumps (PTHP) – (Expanded Recall Feb. – 2017)
Description:
This expanded recall involves Packaged Terminal Air Conditioners (PTAC) and Packaged Terminal Heat Pumps (PTHP) sold under the Bryant, Carrier and Fast brand names. Recalled units include those with original power cords and those that received a replacement power cord as part of the 2007 recall.
The recalled units have capacities of 7,000; 9,000; 12,000 and 15,000 BTUs and plug into 208/230 volt outlets. The following brands and eight models are being recalled:
• Carrier models 52CE, 52CQ, 52PE, 52PQ, 52PC, 52ME, 52MQ;
• Bryant models 840, 841, and 842; and
• Fast models 840, 841, and 842.
Model and serial numbers are located on the ratings/data plate on the right front of the unit, underneath the removable front panel.  A complete list of the serial numbers involved in this recall is available by calling Carrier (800.761.8492).
View Recall

Bryant-Carrier-Fast Packaged Terminal Air Conditioners (PTAC) and Packaged Terminal Heat Pumps (PTHP)

Carrier Brands

Carrier- BW1 & BW2 Series gas-fired boilers – CPSC Recall #02-152 (May. – 2002)
The recalled boilers have the Dunkirk, Sears Kenmore, Bryant, Carrier, Payne, Lennox and Pennco brand names, which is written on the front of the boilers. The model and serial number are located on the data plate located on the right side of the boiler. The following models and serial numbers are included in the recall:

Brand Model Numbers Serial Numbers
Dunkirk/Sears Kenmore PVWB-4 through PVWB-9
PWB4 through PWB9
PWB-4 through PWB-9
PWX-4 through PWX-9
320100007S – 520100299S
010200098S – 090200182S
Lennox GWB8-105E through GWB8-280E
GWB8-105S through GWB8-280S
340100148S – 500100600S
010200199S – 050200279S
Carrier/Bryant/ Payne
BW1AAN000105 – BW1AAN000280
BW1AAP000105 – BW1AAP000280
BW2AAP000105 – BW2AAP000280
3601V04044S – 5201V08708S
0102V000015S – 0902V01118S
Pennco 1504HWID and 1509HWID(natural gas)
1504HWD and 1509HWD(natural gas)
1502HWID – 1509HWID (LPgas only)
1502HWD – 1509HWD (LP gas only)
90131-0924 through 90152-0424
90201-0421 through 90208-0424

Independent heating contractors sold and installed these boilers nationwide from August 2001 through March 2002 for between $1,200 and $3,000.

Consumers should contact ECR International immediately to arrange for a free repair. Consumers can call ECR International at (800) 241- 5501 between 8 a.m. and 5 p.m. ET Monday through Friday.

CPSC recommends that every home should have at least one CO alarm that meets the requirements of the most recent Underwriters Laboratories (UL) 2034 standard, International Approval Services 6-96 standard or the Canadian Standards Association 6.19-01 standard.

View Recall

Dunkirk/Sears Kenmore/Lennox/Carrier/Bryant/Payne/Pennco Boilers

Dunkirk/Sears Kenmore/Lennox/Carrier/Bryant/Payne/Pennco Boilers

Century – Packaged Terminal Air Conditioner/Heat Pump (PTAC) units – CPSC Recall #14-263 (Aug. – 2014)
Description:
This recall involves Amana, Century, Comfort-Aire, Goodman and York International-branded Packaged Terminal Air Conditioners and Heat Pumps. The units are rated 230/208 volt, 3.5 kW and are most often installed in walls of hotels, motels, apartment buildings and commercial spaces to provide room climate control. The recalled units are beige with serial numbers ranging from 0701009633 through 0804272329. The brand name is located on the unit’s front cover. The serial number is located on the control board plate found by lifting the unit’s front cover.
View Recall

Amana, Century, Comfort-Aire, Goodman and York International Packaged Terminal Air Conditioner/Heat Pump (PTAC)

Amana, Century, Comfort-Aire, Goodman and York International Packaged Terminal Air Conditioner/Heat Pump (PTAC)

Coleman – Model DGA* Gas furnaces (Mobile Home Furnaces) – CPSC Recall #12-102 (Expanded Recall Feb. – 2012)
Description:
This recall involves Coleman, Coleman Evcon and Red T brand furnaces. The furnaces are silver with white access panels. “Coleman,” “Coleman Evcon” and “Red T” brand names are located on the middle of the front access panel. The model number is written on a faceplate, found by removing both front access panels. The faceplate is found mounted on the left inside surface behind the lower panel. Models included in the recall are:  (See Recall)
View Recall

Coleman, Coleman Evcon and Red T Gas Furnaces for Manufactured Homes

Coleman, Coleman Evcon and Red T Gas Furnaces for Manufactured Homes

Coleman, Coleman Evcon and Red T Gas Furnaces for Manufactured Homes Data Tag

Coleman, Coleman Evcon and Red T Gas Furnaces for Manufactured Homes Data Tag

Coleman Evcon – Model DGA* Gas furnaces (Mobile Home Furnaces) – CPSC Recall #12-102 (Expanded Recall Feb. – 2012)
Description:
This recall involves Coleman, Coleman Evcon and Red T brand furnaces. The furnaces are silver with white access panels. “Coleman,” “Coleman Evcon” and “Red T” brand names are located on the middle of the front access panel. The model number is written on a faceplate, found by removing both front access panels. The faceplate is found mounted on the left inside surface behind the lower panel. Models included in the recall are:  (See Recall)
View Recall

Coleman, Coleman Evcon and Red T Gas Furnaces for Manufactured Homes

Coleman, Coleman Evcon and Red T Gas Furnaces for Manufactured Homes

Coleman, Coleman Evcon and Red T Gas Furnaces for Manufactured Homes Data Tag

Coleman, Coleman Evcon and Red T Gas Furnaces for Manufactured Homes Data Tag

Comfort-Aire – Packaged Terminal Air Conditioner/Heat Pump (PTAC) units – CPSC Recall #14-263 (Aug. – 2014)
Description:
This recall involves Amana, Century, Comfort-Aire, Goodman and York International-branded Packaged Terminal Air Conditioners and Heat Pumps. The units are rated 230/208 volt, 3.5 kW and are most often installed in walls of hotels, motels, apartment buildings and commercial spaces to provide room climate control. The recalled units are beige with serial numbers ranging from 0701009633 through 0804272329. The brand name is located on the unit’s front cover. The serial number is located on the control board plate found by lifting the unit’s front cover.
View Recall

Amana, Century, Comfort-Aire, Goodman and York International Packaged Terminal Air Conditioner/Heat Pump (PTAC)

Amana, Century, Comfort-Aire, Goodman and York International Packaged Terminal Air Conditioner/Heat Pump (PTAC)

Crown Boiler – CWD series cast iron hot water boilers that use natural gas or liquid petroleum. – CPSC Recall #14-035 (Dec. – 2013)
Description:
This recall involves Crown Boiler CWD series cast iron hot water boilers that use natural gas or liquid petroleum to heat water in home baseboard, floor or radiator heating systems. The boilers are red and gray, about 37 inches tall, about 23 inches deep and range from about 16 to 42 inches wide. The Crown Boiler logo is on the front of the boiler. Recalled boilers have model numbers that begin with CWD and were manufactured between May 1, 2005 and July 1, 2013. The model number and the manufacturing date are located on a white rating label located on the upper right side of the boiler. The manufacturing date appears under “Series” in the MM/DD/YYYY or M/D/YYYY format or as a two-letter code. Recalled models have dates between 5/1/2005 and 7/1/2013 or one of the following two-letter codes:
EB, FB, GB, HB, IB, JB, KB, LB
AC, BC, CC, DC, EC, FC, GC, HC, IC, JC, KC, LC
AD, BD, CD, DD, ED, FD, GD, HD, ID, JD, KD, LD
AE, BE, CE, DE, EE, FE, GE, HE, IE, JE, KE, LE
AF, BF, CF, DF, EF, FF, GF, HF, IF, JF, KF, LF
AG, BG, CG, DG, EG, FG, GG, HG, IG, JG, KG, LG
AH, BH, CH, DH, EH, FH, GH, HH, IH, JH, KH, LH
AI, BI, CI, DI, EI, FI, GI, HI, II, JI, KI, LI
AJ, BJ, CJ, DJ, EJ, FJ.
View Recall

Recalled Crown CWD series natural gas and liquid petroleum hot water boilers

Crown CMD Series Cast Iron Boiler

Recalled Crown CWD series data tag

Crown CMD Series Cast Iron Boiler data tag

Crown Boiler – Bermuda BSI and Cayman CWI series gas boilers. – CPSC Recall #07-063 (Originally Released Dec – 2006 / Revised Release Oct. – 2012)
Name of Product: Bermuda BSI and Cayman CWI Series Gas Boilers
Units: About 400
Manufacturer: Crown Boiler Co., of Philadelphia, Pa.
Hazard: The boilers can generate excessive levels of carbon monoxide (CO) in the flue gases, posing a risk of CO poisoning.
Incidents/Injuries: Crown Boiler has received one report of high levels of carbon monoxide from these boilers. No injuries have been reported.
Description: The recall involves Bermuda BSI and Cayman CWI Series gas-fired boilers designed for indoor installation. Model and serial numbers included in this recall are listed below and are located on the rating plate. The boilers have a two-tone, red and gray jacket enclosure with the controls and piping on the right side of the unit. The rating plate is a silver label located in the upper left hand corner of the right side panel.
Model Numbers
Serial Numbers
BSI069SN
CROWNB000304258
and
CROWNB000411446
BSI069EN
BSI172SL
BSI172EL
CWI069SN
CWI069EN
CWI172SL
CWI172EL
 
Sold by: Plumbing and heating wholesale distributors to plumbers and contractors nationwide from October 2002 through October 2006 for between $800 and $2,100.
Manufactured in: United States
Remedy: Consumers who have not already been contacted by their contractor should immediately contact their installer or Crown Boiler Co. to arrange for a free repair. Consumers are reminded to install a CO alarm outside all sleeping areas, or make sure their current CO alarms have working batteries.
 Consumer Contact: For more information, contact Crown Boiler Co at (215) 535-8900 between 8 a.m. and 5 p.m. ET Monday through Friday, or visit the firm’s Web site at www.crownboiler.com
View Recall

Recalled Crown Bermuda BSI Series Gas Boilers

Crown Recalled Bermuda BSI Series Gas Boiler

Recalled Crown Cayman CWI Series Gas Boiler

Crown Cayman CMI Series Gas Boiler

Daikin – DM80HE Series Furnaces – CPSC Recall #17-145 (May. – 2017)
Description:
This recall involves 80% efficiency gas-fired furnaces sold under the Goodman, Amana and Daikin brand names used with home heating and cooling systems. The recalled products have model numbers beginning AMEH80, DM80HE, and GME8, and serial numbers beginning 1609, 1610, 1611 and 1612. The brand name is shown on the outside of the furnace, and the serial number is located on the label found by opening the furnace door.
View Recall

Daikin DM80HE furnace

Daikin DM80HE furnace

Daikin DM80HE furnace data tag with model and serial number would be similar to this Goodman tag.

Goodman Brand Furnace Data Tag

Dayton – Model 3UG82D Electric Baseboard Heaters – CPSC Recall #10-745 (Jul. – 2010)
Description:
Name of Product: Dayton Electric Baseboard Heaters

Units: About 30

Manufacturer: Marley Engineered Products LLC, of Bennettsville, S.C.

Hazard: The baseboard heaters are labeled for 240 or 208 volt use. However, some of the heaters have an internal heater built for a maximum of 120 volts. If the heater is connected to a 240 or 208 volt electrical circuit as directed, the unit could catch fire.

Incidents/Injuries: None reported.

Description: This recall involves Dayton 240/208 volt model 3UG82D electric baseboard heaters. The white, rectangular heaters are 30 inches long by 6 3/4 inches high by 2 7/8 inches deep. A nameplate on the bottom right side of the base has “Dayton Electric Mfg. Co.,” model 3UG82D and date code 1209. Only heaters purchased after December 21, 2009 with a date code of “1209” are included in this recall. The recalled heaters have yellow and white wires inside the panel where the heater connects to the power source. Heaters with red and black wire are not included in this recall.

Sold exclusively at: Grainger branch stores nationwide from December 2009 through March 2010 for about $50.

Manufactured in: United States

Remedy: Consumers should immediately stop using the heaters and inspect the product’s nameplate to determine whether it is involved in the recall. Consumers with affected heaters should disconnect the product at the circuit breaker or fuse. A qualified electrician should inspect the color of the wires inside the heater’s electrical access panel to determine if the wires are yellow and white. Consumers should return the affected heaters to Marley for a free replacement. Marley will pay reasonable labor charges required to inspect and exchange units. Marley is directly notifying known consumers.

View Recall

Dayton Model 3UG82D Electric Baseboard Heater Recall

Dayton Model 3UG82D Electric Baseboard Heater Recall

Dayton Model 3UG82D Electric Baseboard Heater Recall data tag .

Dayton Model 3UG82D Electric Baseboard Heater Recall Data Tag

Dunkirk- PVWB-*; PWB*; PWB-*; and PWX-* Series gas-fired boilers – CPSC Recall #02-152 (May. – 2002)
The recalled boilers have the Dunkirk, Sears Kenmore, Bryant, Carrier, Payne, Lennox and Pennco brand names, which is written on the front of the boilers. The model and serial number are located on the data plate located on the right side of the boiler. The following models and serial numbers are included in the recall:

Brand Model Numbers Serial Numbers
Dunkirk/Sears Kenmore PVWB-4 through PVWB-9
PWB4 through PWB9
PWB-4 through PWB-9
PWX-4 through PWX-9
320100007S – 520100299S
010200098S – 090200182S
Lennox GWB8-105E through GWB8-280E
GWB8-105S through GWB8-280S
340100148S – 500100600S
010200199S – 050200279S
Carrier/Bryant/ Payne
BW1AAN000105 – BW1AAN000280
BW1AAP000105 – BW1AAP000280
BW2AAP000105 – BW2AAP000280
3601V04044S – 5201V08708S
0102V000015S – 0902V01118S
Pennco 1504HWID and 1509HWID(natural gas)
1504HWD and 1509HWD(natural gas)
1502HWID – 1509HWID (LPgas only)
1502HWD – 1509HWD (LP gas only)
90131-0924 through 90152-0424
90201-0421 through 90208-0424

Independent heating contractors sold and installed these boilers nationwide from August 2001 through March 2002 for between $1,200 and $3,000.

Consumers should contact ECR International immediately to arrange for a free repair. Consumers can call ECR International at (800) 241- 5501 between 8 a.m. and 5 p.m. ET Monday through Friday.

CPSC recommends that every home should have at least one CO alarm that meets the requirements of the most recent Underwriters Laboratories (UL) 2034 standard, International Approval Services 6-96 standard or the Canadian Standards Association 6.19-01 standard.

View Recall

Dunkirk/Sears Kenmore/Lennox/Carrier/Bryant/Payne/Pennco Boilers

Dunkirk/Sears Kenmore/Lennox/Carrier/Bryant/Payne/Pennco Boilers

Fast – Packaged Terminal Air Conditioners (PTAC) and Heat Pumps (PTHP) – (Expanded Recall Feb. – 2017)
Description:
This expanded recall involves Packaged Terminal Air Conditioners (PTAC) and Packaged Terminal Heat Pumps (PTHP) sold under the Bryant, Carrier and Fast brand names. Recalled units include those with original power cords and those that received a replacement power cord as part of the 2007 recall.
The recalled units have capacities of 7,000; 9,000; 12,000 and 15,000 BTUs and plug into 208/230 volt outlets. The following brands and eight models are being recalled:
• Carrier models 52CE, 52CQ, 52PE, 52PQ, 52PC, 52ME, 52MQ;
• Bryant models 840, 841, and 842; and
• Fast models 840, 841, and 842.
Model and serial numbers are located on the ratings/data plate on the right front of the unit, underneath the removable front panel.  A complete list of the serial numbers involved in this recall is available by calling Carrier (800.761.8492).
View Recall

Bryant-Carrier-Fast Packaged Terminal Air Conditioners (PTAC) and Packaged Terminal Heat Pumps (PTHP)

Carrier Brands

Goodman – AWUF & ACNF Series Air Handlers – CPSC Recall #17-103 (Mar. – 2017)
Description:
This recall involves Goodman air handler models AWUF and ACNF (A = Air Handler; W = Wall Mount; C = Ceiling Mount; U = Unpainted; N = Uncased; F = Flowrater). The recalled air handlers are most often installed in apartment and condominium units and are used with heating and cooling systems to provide climate control. The AWUF model units are wall mounted, while ACNF model units are ceiling mounted. The recalled air handlers have serial numbers beginning with 1511, 1512, or 1601 through 1610. The serial number is located on the label found by removing the wall panel (for AWUF units) or ceiling panel (for ACNF units).  Primarily used by Apartment complexes, townhouse and condominium associations and individuals that generally purchased units as part of a bundled product.
View Recall

Goodman AWUF & ACNF Air Handlers

Goodman AWUF & ACNF Air Handlers

Goodman – GME8 Series Furnaces – CPSC Recall #17-145 (May. – 2017)
Description:
This recall involves 80% efficiency gas-fired furnaces sold under the Goodman, Amana and Daikin brand names used with home heating and cooling systems. The recalled products have model numbers beginning AMEH80, DM80HE, and GME8, and serial numbers beginning 1609, 1610, 1611 and 1612. The brand name is shown on the outside of the furnace, and the serial number is located on the label found by opening the furnace door.
View Recall

Goodman GME8 furnace

Goodman GME8 furnace

Goodman GME8 furnace data tag’.

Goodman Brand Furnace Data Tag

Goodman – Packaged Terminal Air Conditioner/Heat Pump (PTAC) units – CPSC Recall #14-263 (Aug. – 2014)
Description:
This recall involves Amana, Century, Comfort-Aire, Goodman and York International-branded Packaged Terminal Air Conditioners and Heat Pumps. The units are rated 230/208 volt, 3.5 kW and are most often installed in walls of hotels, motels, apartment buildings and commercial spaces to provide room climate control. The recalled units are beige with serial numbers ranging from 0701009633 through 0804272329. The brand name is located on the unit’s front cover. The serial number is located on the control board plate found by lifting the unit’s front cover.
View Recall

Amana, Century, Comfort-Aire, Goodman and York International Packaged Terminal Air Conditioner/Heat Pump (PTAC)

Amana, Century, Comfort-Aire, Goodman and York International Packaged Terminal Air Conditioner/Heat Pump (PTAC)

Laars – 9600 CB Condensing Boilers- CPSC Recall #07-535 (Mar. – 2007)
Name of Product: Laars 9600 CB Condensing Boilers & 9600 HWG Condensing Water Heaters
Units: About 2,100
Manufacturer: Laars Heating Systems Co., of Rochester, N.H.
Hazard: Internal black plastic venting components in the gas boilers and water heaters can crack and leak flue gases, including carbon monoxide (CO), posing a risk of CO poisoning.
Incidents/Injuries: Laars has received three reports of cracked vent components. No injuries have been reported.
Description: This recall involves Laars 9600 CB Condensing Heating Boilers and Laars 9600 HWG Condensing Water Heaters with black vent pipe/tubing. The recalled boilers are used to generate hot water for heating systems including baseboards or radiant flooring. The recalled water heaters generate hot water for use in homes, such as showers, sinks and dishwashers. “Mark II” and “9600 CB” or “9600 HWG” are printed on the front of the boilers and water heaters. The model number and BTU size are printed on the right side of the unit. The recalled boiler and water heater exteriors are putty and black-colored or taupe and black-colored. Only the following models are included in this recall.
Model Input (Btu/h)
Gas Boilers:
CB 150 150,000
CB 175 175,000
CB 200 200,000
Water Heaters:
HWG 150 150,000
HWG 175 175,000
HWG 200 200,000
Sold at: Plumbing and heating wholesalers and representatives nationwide from November 1998 through February 2007 for between $6,500 and $7,300.
Manufactured in: United States
Remedy: Consumers should contact Laars Heating Systems to help determine if their boiler or water heater needs to be shut off immediately and to schedule a free repair.
Consumer Contact: Contact Laars Service Department at (800) 900-9276, Extension 4, between 7 a.m. and 4 p.m. PT Monday through Friday, or visit the firm’s Web site at www.Laars.com
View Recall

Laars 9600 CB Condensing Boiler Front View

Laars 9600 CB Condensing Boiler

Laars 9600 CB Condensing Boiler Side View

Laars 9600 CB Condensing Boiler

Laars 9600 CB Condensing Boiler Black Vent Pipe/Tubing

Laars 9600 CB Condensing Boiler Black Vent Pipe/Tubing

Lennox – TUA Series Unit Heaters – CPSC Recall #11-198 (Apr. – 2011)
Description and Models:

Description:

This recall involves Lennox garage heaters with heating capacity, model number, and serial number listed below. The brand name “”Lennox””, the model number and the serial number can be found on the nameplate located inside the control cabinet.

Heating Capacity Model Number Serial Number Range

60,000 BTUH TUA060SNAF1 5609H#### to 5610M#####

100,000 BTUH TUA100SNAF1 6004G#### to 6010L##### and
5604G#### to 5610L#####

100,000 BTUH TUA100SNSF1 6004G#### to 6010L##### and
5604G#### to 5610L#####

125,000 BTUH TUA125SNAF1 6004G#### to 6010L##### and
5604G#### to 5610L#####

125,000 BTUH TUA125SNSF1 6004G#### to 6010L##### and
5604G#### to 5610L#####

Remedy:

Consumers should stop using these recalled heaters immediately. Consumers should contact Lennox to schedule an inspection and, if necessary, repair of the garage heater.

Incidents/Injuries:

None reported.
Sold At:

Lennox Industries dealers and distributors nationwide from July 2004 through April 2011 for between $2,700 and $4,200.
Manufacturer(s):
Lennox Industries Inc., of Richardson, Texas or Advanced Distributor Products (ADP) LLC, of Grenada, Miss.
Distributor(s):

Lennox Industries Inc., of Richardson, Texas

View Recall

ADP FOA series and Lennox TOA series unit heater recall

ADP FOA series and Lennox unit heater recall

ADP FOA series and Lennox TOA unit heater data tag.

ADP FOA series and Lennox unit heater Data Tag

Lennox- GWB Series gas-fired boilers – CPSC Recall #02-152 (May. – 2002)
The recalled boilers have the Dunkirk, Sears Kenmore, Bryant, Carrier, Payne, Lennox and Pennco brand names, which is written on the front of the boilers. The model and serial number are located on the data plate located on the right side of the boiler. The following models and serial numbers are included in the recall:

Brand Model Numbers Serial Numbers
Dunkirk/Sears Kenmore PVWB-4 through PVWB-9
PWB4 through PWB9
PWB-4 through PWB-9
PWX-4 through PWX-9
320100007S – 520100299S
010200098S – 090200182S
Lennox GWB8-105E through GWB8-280E
GWB8-105S through GWB8-280S
340100148S – 500100600S
010200199S – 050200279S
Carrier/Bryant/ Payne
BW1AAN000105 – BW1AAN000280
BW1AAP000105 – BW1AAP000280
BW2AAP000105 – BW2AAP000280
3601V04044S – 5201V08708S
0102V000015S – 0902V01118S
Pennco 1504HWID and 1509HWID(natural gas)
1504HWD and 1509HWD(natural gas)
1502HWID – 1509HWID (LPgas only)
1502HWD – 1509HWD (LP gas only)
90131-0924 through 90152-0424
90201-0421 through 90208-0424

Independent heating contractors sold and installed these boilers nationwide from August 2001 through March 2002 for between $1,200 and $3,000.

Consumers should contact ECR International immediately to arrange for a free repair. Consumers can call ECR International at (800) 241- 5501 between 8 a.m. and 5 p.m. ET Monday through Friday.

CPSC recommends that every home should have at least one CO alarm that meets the requirements of the most recent Underwriters Laboratories (UL) 2034 standard, International Approval Services 6-96 standard or the Canadian Standards Association 6.19-01 standard.

View Recall

Dunkirk/Sears Kenmore/Lennox/Carrier/Bryant/Payne/Pennco Boilers

Dunkirk/Sears Kenmore/Lennox/Carrier/Bryant/Payne/Pennco Boilers

New Yorker Boiler – PVCG model gas-fired cast iron hot water boiler units – CPSC Recall #14-077 (Jan. – 2014)
Description:
This recall involves New Yorker Boiler PVCGA model cast iron hot water boilers that use natural gas or liquid petroleum to heat water for residential space heating. The boilers are green in color, about 38 inches tall and about 26 inches deep and range from 11 to 30 inches wide. The front cover of the boiler is vented and has the New Yorker Boiler logo. Recalled boilers were manufactured between May 2012 and February 2013. The model number, serial number and manufacturing date are located on a silver label on the inside panel. The manufacturing date appears in the upper right corner of the silver label in the MM/YYYY format. The following model numbers and serial number ranges are included in this recall:  See recall below.
View Recall

New Yorker Boiler – PVCG Model

New Yorker Boiler-PVCG Model

New York Thermal (NTI) Boiler – NTI Trinity gas-fired hot water boiler units – CPSC Recall #07-151 (Apr. – 2007)
Name of product: NTI Trinity Gas-Fired Hot Water Boilers
Units: About 4,800
Distributor: NY Thermal Inc., of Sussex, New Brunswick, Canada
Hazard: Acidic liquid in a drain line can cause a fitting in the boiler to leak, posing a risk of carbon monoxide (CO) poisoning to consumers.
Incidents/Injuries: NY Thermal Inc. has received one report outside of the United States of a leaking fitting resulting in a CO alarm activation. No injuries have been reported.
Description: The recall includes NTI Trinity gas-fired hot water boilers with model numbers Ti100, Ti150, Ti200 and Ti400. The boilers were manufactured between November 28, 2005 and January 8, 2007. The Ti100, Ti150 and Ti200 are wall-mounted units, and the Ti400 rests on the floor. The boilers are gray in color and “NTI” appears on the front cover. The model number and date of manufacture are located on the ID label inside the front cover of the boiler.
Sold by: Plumbing and heating contractors nationwide from November 2005 through February 2007 for between $3,000 and 8,500, depending on the model.
Manufactured in: Canada
Remedy: Consumers should immediately contact the firm for instructions and to arrange for a free repair.
Consumer Contact: For more information, contact NY Thermal Inc. at (800) 688-2575 between 7 a.m. and 4 p.m. ET Monday through Friday, or visit the firm’s Web site at www.nythermal.com.
View Recall

NTI Trinity gas-fired boiler

NTI Trinity gas-fired boilerl

NTI Trinity gas-fired boiler data plate

NTI Trinity gas-fired boiler data plate

Payne- BW1 & BW2 Series gas-fired boilers – CPSC Recall #02-152 (May. – 2002)
The recalled boilers have the Dunkirk, Sears Kenmore, Bryant, Carrier, Payne, Lennox and Pennco brand names, which is written on the front of the boilers. The model and serial number are located on the data plate located on the right side of the boiler. The following models and serial numbers are included in the recall:

Brand Model Numbers Serial Numbers
Dunkirk/Sears Kenmore PVWB-4 through PVWB-9
PWB4 through PWB9
PWB-4 through PWB-9
PWX-4 through PWX-9
320100007S – 520100299S
010200098S – 090200182S
Lennox GWB8-105E through GWB8-280E
GWB8-105S through GWB8-280S
340100148S – 500100600S
010200199S – 050200279S
Carrier/Bryant/ Payne
BW1AAN000105 – BW1AAN000280
BW1AAP000105 – BW1AAP000280
BW2AAP000105 – BW2AAP000280
3601V04044S – 5201V08708S
0102V000015S – 0902V01118S
Pennco 1504HWID and 1509HWID(natural gas)
1504HWD and 1509HWD(natural gas)
1502HWID – 1509HWID (LPgas only)
1502HWD – 1509HWD (LP gas only)
90131-0924 through 90152-0424
90201-0421 through 90208-0424

Independent heating contractors sold and installed these boilers nationwide from August 2001 through March 2002 for between $1,200 and $3,000.

Consumers should contact ECR International immediately to arrange for a free repair. Consumers can call ECR International at (800) 241- 5501 between 8 a.m. and 5 p.m. ET Monday through Friday.

CPSC recommends that every home should have at least one CO alarm that meets the requirements of the most recent Underwriters Laboratories (UL) 2034 standard, International Approval Services 6-96 standard or the Canadian Standards Association 6.19-01 standard.

View Recall

Dunkirk/Sears Kenmore/Lennox/Carrier/Bryant/Payne/Pennco Boilers

Dunkirk/Sears Kenmore/Lennox/Carrier/Bryant/Payne/Pennco Boilers

PB Heat Boiler – DE and PSC II series gas-fired cast iron boilers with the Endura Plastics Model ES2035 pressure switch – CPSC Recall #08-397 (Sep. – 2008)
Name of Product: Gas Boilers
Units: About 1,200
Manufacturer: PB Heat LLC, of Bally, Pa.
Hazard: The pressure switch could have an internal defect that could fail to shut down the boilers under vent or air inlet blockage. This switch defect could allow the boilers to produce excessive levels of carbon monoxide, posing a risk of carbon monoxide poisoning to consumers.
Incidents/Injuries: None reported.
Description: This recall involves the DE and PSC II Gas Fired Cast Iron Boilers with the Endura Plastics Model ES2035 pressure switch used for home heating and domestic hot water heating. The boilers were available in either natural or LP gas. The boiler rating label is located on the top jacket panel on Series PSCII models and the left side jacket panel on the Series DE models. The label includes the model and serial number. The following model names and serial numbers are included in the recall:
Model Name Serial Number
DE-03, DE-04, DE-05 and DE-06 5040768 to 5052860
PSCII-03, PSCII-04, PSCII-05, and PSCII-06 5040777 to 5052166
Other suffix designation may follow the base model number such as SV-WPC.
Sold at: Plumbing and heating wholesale distributors nationwide from May 2007 through July 2008 for between $1,800 and $3,000.
Manufactured in: United States
Remedy: Consumers who have not already been contacted, should contact their installer immediately for a free safety inspection and repair, if necessary.
Consumer Contact: For more information, consumers can contact PB Heat toll-free at (877) 257-3300 between 8 a.m. and 4 p.m. ET Monday through Friday or visit the firm’s Web site at www.peerlessboilers.com
View Recall

PB Heat Series DE Boiler

PB Heat Series DE Boiler

PB Heat Series PSCII Boiler

PB Heat Series PSCII Boiler

Pennco- HWID & HWD Series gas-fired boilers – CPSC Recall #02-152 (May. – 2002)
The recalled boilers have the Dunkirk, Sears Kenmore, Bryant, Carrier, Payne, Lennox and Pennco brand names, which is written on the front of the boilers. The model and serial number are located on the data plate located on the right side of the boiler. The following models and serial numbers are included in the recall:

Brand Model Numbers Serial Numbers
Dunkirk/Sears Kenmore PVWB-4 through PVWB-9
PWB4 through PWB9
PWB-4 through PWB-9
PWX-4 through PWX-9
320100007S – 520100299S
010200098S – 090200182S
Lennox GWB8-105E through GWB8-280E
GWB8-105S through GWB8-280S
340100148S – 500100600S
010200199S – 050200279S
Carrier/Bryant/ Payne
BW1AAN000105 – BW1AAN000280
BW1AAP000105 – BW1AAP000280
BW2AAP000105 – BW2AAP000280
3601V04044S – 5201V08708S
0102V000015S – 0902V01118S
Pennco 1504HWID and 1509HWID(natural gas)
1504HWD and 1509HWD(natural gas)
1502HWID – 1509HWID (LPgas only)
1502HWD – 1509HWD (LP gas only)
90131-0924 through 90152-0424
90201-0421 through 90208-0424

Independent heating contractors sold and installed these boilers nationwide from August 2001 through March 2002 for between $1,200 and $3,000.

Consumers should contact ECR International immediately to arrange for a free repair. Consumers can call ECR International at (800) 241- 5501 between 8 a.m. and 5 p.m. ET Monday through Friday.

CPSC recommends that every home should have at least one CO alarm that meets the requirements of the most recent Underwriters Laboratories (UL) 2034 standard, International Approval Services 6-96 standard or the Canadian Standards Association 6.19-01 standard.

View Recall

Dunkirk/Sears Kenmore/Lennox/Carrier/Bryant/Payne/Pennco Boilers

Dunkirk/Sears Kenmore/Lennox/Carrier/Bryant/Payne/Pennco Boilers

Red T – Model DGA* Gas furnaces (Mobile Home Furnaces) – CPSC Recall #12-102 (Expanded Recall Feb. – 2012)
Description:
This recall involves Coleman, Coleman Evcon and Red T brand furnaces. The furnaces are silver with white access panels. “Coleman,” “Coleman Evcon” and “Red T” brand names are located on the middle of the front access panel. The model number is written on a faceplate, found by removing both front access panels. The faceplate is found mounted on the left inside surface behind the lower panel. Models included in the recall are:  (See Recall)
View Recall

Coleman, Coleman Evcon and Red T Gas Furnaces for Manufactured Homes

Coleman, Coleman Evcon and Red T Gas Furnaces for Manufactured Homes

Coleman, Coleman Evcon and Red T Gas Furnaces for Manufactured Homes Data Tag

Coleman, Coleman Evcon and Red T Gas Furnaces for Manufactured Homes Data Tag

Sears Kenmore- PVWB-*; PWB*; PWB-*; and PWX-* Series gas-fired boilers – CPSC Recall #02-152 (May. – 2002)
The recalled boilers have the Dunkirk, Sears Kenmore, Bryant, Carrier, Payne, Lennox and Pennco brand names, which is written on the front of the boilers. The model and serial number are located on the data plate located on the right side of the boiler. The following models and serial numbers are included in the recall:

Brand Model Numbers Serial Numbers
Dunkirk/Sears Kenmore PVWB-4 through PVWB-9
PWB4 through PWB9
PWB-4 through PWB-9
PWX-4 through PWX-9
320100007S – 520100299S
010200098S – 090200182S
Lennox GWB8-105E through GWB8-280E
GWB8-105S through GWB8-280S
340100148S – 500100600S
010200199S – 050200279S
Carrier/Bryant/ Payne
BW1AAN000105 – BW1AAN000280
BW1AAP000105 – BW1AAP000280
BW2AAP000105 – BW2AAP000280
3601V04044S – 5201V08708S
0102V000015S – 0902V01118S
Pennco 1504HWID and 1509HWID(natural gas)
1504HWD and 1509HWD(natural gas)
1502HWID – 1509HWID (LPgas only)
1502HWD – 1509HWD (LP gas only)
90131-0924 through 90152-0424
90201-0421 through 90208-0424

Independent heating contractors sold and installed these boilers nationwide from August 2001 through March 2002 for between $1,200 and $3,000.

Consumers should contact ECR International immediately to arrange for a free repair. Consumers can call ECR International at (800) 241- 5501 between 8 a.m. and 5 p.m. ET Monday through Friday.

CPSC recommends that every home should have at least one CO alarm that meets the requirements of the most recent Underwriters Laboratories (UL) 2034 standard, International Approval Services 6-96 standard or the Canadian Standards Association 6.19-01 standard.

View Recall

Dunkirk/Sears Kenmore/Lennox/Carrier/Bryant/Payne/Pennco Boilers

Dunkirk/Sears Kenmore/Lennox/Carrier/Bryant/Payne/Pennco Boilers

Trane – Furnaces – CPSC Recall #17-709 (Nov. – 2016)
Description:
This recall involves Trane, American Standard, Ameristar brand or unbranded furnaces. The recalled furnaces include serial numbers beginning with 16304 through 16324. The model and serial numbers are printed on a white label on the left or right-hand side of the unit. The following model numbers are included in the recall:  (See Recall for complete list).
View Recall

Trane furnace

Trane Brands

Trane furnace data tag with model and serial number

Trane Brands Data Tag

Trane – XB300 Outdoor Unit Air Conditioner – CPSC Recall #14-737 (Jun. – 2014)
Description:
This recall involves 37 models of Trane XB300 and American Standard brand Silver SI split system outdoor cooling units. The units are gray and have a black grated front. The units were sold in two sizes: 25.5 inches deep by 23.5 inches wide by 28.83 inches tall and 28.83 inches deep by 28.48 inches wide by 29.28 inches tall. The Trane or American Standard logo is affixed to the front and model numbers are printed on the silver nameplate on the back of the unit. Models included in the recall are::  (See Recall for complete list).
View Recall

Trane XB300 Outdoor Unit Air Conditioner Front

Trane XB300

Trane XB300 Outdoor Unit Air Conditioner Back

Trane XB300

U.S. Boiler – Gas-fired hot water boilers, model(s) ESC, PVG and SCG – CPSC Recall #14-076 (Jan. – 2014)
Description:
This recall involves U.S. Boiler ESC, PVG and SCG model cast iron hot water boilers that use natural gas or liquid petroleum to heat water for residential space heating. The boilers are light blue in color with black trim, about 40 inches tall, about 26 inches deep and range from 12 to 31 inches wide. The model name and U.S. Boiler logo are on the front cover of the boiler. The front cover of the boiler is vented. Recalled boilers were manufactured between December 2005 and February 2013. The model number, serial number and manufacturing date are located on a silver label on the top panel of ESC models and on the inside of PVG and SCG models on the right side panel. The manufacturing date appears in the upper right corner of the silver label in the MM/YYYY format.  The following model numbers and serial number ranges are included in this recall:
Model Number
Serial Number Range
ESC3 through ESC9
65249110 through 65382278
PVG3_P, PVG4_P and PVG5 through PVG9
64870666 through 65385748; 97939433
SCG3 through SCG9
35200197; 65283322 through 65858729
View Recall

U.S. Boiler Model ESC rating label location

U.S. Boiler Model ESC

U.S. Boiler Model(s) PVG/SCG boiler rating label location

U.S. Boiler Models PVG/SCG

Viessmann – Vitodens 200-W Gas Boiler – CPSC Recall #16-729 (Feb. – 2016)
Description:
This recall involves the Vitodens 200-W condensing gas boilers used for residential use. These wall hung units are housed in a white metal box that measures about 43.5 inches tall by 19 inches wide by 21 inches deep. There are two models: B2HB-45 and B2HB-57 included in this recall. The name “Vitodens” and “Viessmann” are printed on the label on the outside of the boiler box. The product name and model number can be found on the boiler rating plate located on the left side of the white boiler cover. The serial number can be found on a separate label under the boiler cover or on the left hand side of the unit. Recalled boilers do not have a blue dot with a handwritten data label on it.
The two models of boilers included in the recall have the following serial number ranges:
Product Name
Model Numbers
Serial Number Range
Vitodens 200-W
B2HB-45
7554703501001105 to 7554703501369106 *
B2HB-57
7554704501001102 to 7554703501411109 *
* Serial number range within bold number range are the only units included in the recall.
View Recall

Vitodens 200-W Gas Boiler

Vitodens 200-W Gas Boiler

Location of serial number under white cover

Vitodens 200-W Gas Boiler Data Sticker

Location of serial number under the boiler

Vitodens 200-W Gas Boiler Data Sticker

Viessmann – Vitodens 200 Gas Boiler – CPSC Recall #09-002 (Oct. – 2008)
Name of Product: Vitodens 200 Boilers

Units: About 4,600

Manufacturer: Viessmann Manufacturing Co. Inc., of Canada

Hazard: The boiler can leak gas, posing a fire hazard to consumers.

Incidents/Injuries: None reported.

Description: The recall involves the Vitodens 200 boiler. The gas-fired boilers are white, wall-mounted and have “Viessmann” and “Vitodens 200” printed on the exterior in silver letters. The model and serial numbers included in the recall are listed below. The model number is located on the silver rating plate on the side of the boiler. Contact your certified HVAC contractor to open the boiler and locate the serial number on a white label on the side of the boiler, or under the bottom support panel. Vitodens 100 boilers are not included in this recall.

Model Number Serial Number Additional Information
WB2 6-24C 7167063xxxxxxxxx or 7170317xxxxxxxxx If the serial number’s 8th digit
(listed in red) is a 2, 3, 4, 5 or
6, the boiler is included in the
recall.
WB2 6-24 7167064xxxxxxxxx or 7170318xxxxxxxxx
WB2 8-32 7167065xxxxxxxxx or 7170319xxxxxxxxx
WB2 11-44 7167066xxxxxxxxx or 7188578xxxxxxxxx
WB2 15-60 7167067xxxxxxxxx or 7188577xxxxxxxxx

Sold by: Plumbing and heating contractors nationwide from January 2002 through December 2007 for between $4,000 and $7,500.

Manufactured in: Canada

Remedy: Consumers should stop using the boilers immediately weather permitting and contact their certified heating contractor or Viessmann for a free replacement of the boiler’s O-ring.

Consumer Contact: For additional information, contact Viessmann U.S. toll-free at (888) 414-9157, visit the firm’s Web site at www.viessmann-us.com, or email the firm at o-ring@viessmann.com

 

View Recall

Viessmann/Vitodens 200 Gas Boiler

vIESSMANN/Vitodens 200 Gas Boiler

Weil-McLain – Ultra models 80, 105, 155 and 230 MBH Ultra Series Boilers – CPSC Recall #14-203 (Jun. – 2014)
Description:
This recall involves Weil-McLain Ultra models 80, 105, 155 and 230 MBH gas-fired boilers used for space heating. The boilers have a serial number range between CP 6557046 and CP 6955985. Model and serial numbers are located on a bar-coded label affixed to the lower right side of the boiler, behind the removable front panel. The boilers have a Weil-McLain logo plate affixed to the front, a pewter/flat black cover and are either freestanding or wall-mounted.
View Recall

Weil-McLain Ultra Series Boilers

Vitodens 200-W Gas Boiler

Weil-McLain -CGs and CGi Gas Boilers- CPSC Recall #08-566 (May – 2008)
Name of Product: Weil-McLain CGs and CGi Gas Boilers
Units: About 32,000
Manufacturer: Weil-McLain, of Michigan City, Ind.
Hazard: If there is a leak in the vent piping, the recalled boilers can leak carbon monoxide (CO) into the buildings in which they are installed, posing a risk of CO poisoning.
Incidents/Injuries: None reported.
Description: : The recall involves cast iron, gas-fired boilers used for space heating. The following model names and serial numbers are included in the recall.
Model Name Serial Numbers
CGs-3, CGs-4, CGs-5, CGs-6 From CP 5071501 through CP 5694976
CGi-3, CGi-5, CGi-6 Series 2 From CP 4134351 through CP 5698635
The model name and serial number are located on separate labels on the outside of the left panel.
Sold by: Plumbing and heating wholesale distributors to plumbers and contractors nationwide from October 2001 through December 2007 for between $1,700 and $2,700.
Manufactured in: United States
Remedy: Consumers who have not already been contacted, should contact their installer for a free safety inspection and repair, if necessary.
Consumer Contact: For more information, contact Weil-McLain toll-free at (866) 783-9276 between 8 a.m. and 4 p.m. CT Monday through Friday, or visit the firm’s Web site at www.weil-mclain.com
View Recall

Weil-McLain CGs and CGi Boilers

Weil-McClain CGs and CGi Gas Boiler

Weil-McLain -Model 80, 88, 94, and LGB Packaged Commercial Boilers – CPSC Recall #07-521 (Jan. – 2007)
Description:
The recall involves the Weil-McLain Model 80, 88, 94, and LGB Packaged Commercial Boilers built from December 1, 2005 through October 26, 2006. The model information is written on a name plate or rating label on the front blue sheet metal jacket panels.
Sold at: The products were purchased from Weil-McLain and shipped to job sites per boiler order shipping instructions.
View Recall
Sorry. No photos available at this time.
Weil-McLain -Ultra Series Gas Boilers, Model 80, 105, 155, 230 and 310 condensing, high-efficient, gas-fired boilers for space heating. – CPSC Recall #07-020 (Oct.. – 2006)
Name of Product: Weil-McLain Ultra Series Gas Boilers
Units: About 16,000
Manufacturer: Weil-McLain, of Michigan City, Ind.
Hazard: These boilers were manufactured for use with natural gas, but could have a blue tag incorrectly indicating to installers that they are intended for use with LP (propane) gas. If an installer connects one of the boilers to LP gas without installing a propane conversion kit, carbon monoxide (CO) can build up due to incomplete combustion, posing a risk of CO poisoning.
Incidents/Injuries: Weil-McLain is aware of one incident where two consumers reported CO poisoning when the boiler installed in their home was connected to LP gas.
Description: The recall involves Weil-McLain Ultra 80, Ultra 105, Ultra 155, Ultra 230 and Ultra 310 condensing, high-efficient, gas-fired boilers for space heating. The user’s manual and installation manual have “Ultra Gas-Fired Water Boiler” on the cover. The boilers are wrapped in a glossy silver/flat black jacket and either stand on the floor or are wall-mounted. The serial numbers range from CP5071716 through CP5327000. When the panel on the front of the boiler is removed, a bar-coded label with the serial number is located on the lower right hand side of the boiler itself. “Weil-McLain” is written on the front panel of the boilers.
Sold by: Plumbing and heating wholesale distributors to plumbers and contractors nationwide from May 2005 through July 2006 for between $4,000 and $7,000.
Manufactured in: United States
Remedy: Consumers who had a Weil-McLain Ultra series boiler installed for use with propane and have not already been contacted by their installer should contact the installer or a heating professional for a free safety inspection. If the boiler was not installed with a propane conversion kit, one will be installed at the time of the inspection at no charge. Heating professionals may contact Weil McLain Technical Service at (219) 879-6561 for more information.
Consumer Contact: For more information, call Weil-McLain toll-free at (866) 426-6172 between 8 a.m. and 4 p.m. CT Monday through Friday, or visit the firm’s Web site at www.weil-mclain.com
View Recall

Weil-McLain Ultra Series Boiler CP # Location

Weil-McLain Ultra Series Boiler CP # Location

Weil-McLain Recalled Ultra Series Boiler

Weil-McLain recalled Ultra Series Boiler

Weil-McLain Recalled Ultra Series Boiler Cover Removal

Weil-McLain recalled Ultra Series Boiler Cover Removal

Weil-McLain GV Series Boilers – CPSC Recall #06-527 (Feb. – 2006)
Name of Product: GV Series Boilers
Units: 1,131
Manufacturer: Weil-McLain Company, of Michigan City, Ind.
Hazard: The blower assembly is not properly sealed. Gas can leak during operation and accumulate. If an ignition source is present, a fire or explosion could occur.
Incidents/Injuries: No reports of incidents or injuries.
Description: Weil-McClain GV water boiler Models GV-3, GV-4, GV-5 and GV-6 with a serial number/date code range of CP5075477 to CP5221234 and built from April 1, 2005 through October 31, 2005. Serial numbers and date codes are located on the left side of the jacket, above the boiler rating label.
Sold at: Plumbing and heating wholesale companies to independent plumbing heating contractors. Price to consumer (not installed) may range from about $2,200 to $3,200.
Manufactured In: U.S.A.
Remedy: Weil-McLain repaired all recalled boilers at no cost to consumers.
Consumer Contact: Call Weil-McLain at (219) 879-6561 between 8 a.m. to 4 p.m. CT, Monday through Friday, and ask for Consumer Relations, or visit the firm’s Web site at www.weil-mclain.com
View Recall

Weil-McLain GV3 Series Sketch

Weil-McLain Ultra 155 & 230 Boilers – CPSC Recall #03-540 (May. – 2003)
Name of PRODUCT: Ultra 155 & Ultra 230 Gas Boilers

Units: 1,700

Manufacturer: The Weil-McLain Company of Michigan City, Ind.

Hazard: Weil-McLain has determined that the gas valve mounting screws on the recalled boilers may have not been fully tightened during the assembly process and may have come loose in transportation. Weil-McLain is concerned that loose gas fittings could result in leaking gas, fire and/or explosions that could cause bodily injuries or property damage.

INCIDENTS/INJURIES: None reported.

Description: The Ultra 155 & Ultra 230 Gas Boilers are condensing high- efficient gas-fired boilers for space heating. They have 93% operating efficiency and use a cast aluminum, mono block heat exchanger packaged in a glossy silver/flat black jacket.

Sold: Nationally at plumbing and heating wholesale distributors to plumbers and contractors from December 2002 through February 2003 for approximately $4500.

WHAT TO DO: Weil-McLain is providing distributors and installers with a “Safety Notice” package for each boiler containing instructions, replacement screws and a reimbursement form. Installers are also asked to tighten the gas valve union. Installers will be reimbursed $50 for each boiler they inspect.

Consumer Contact: Call Weil-McLain at 219-879-6561 between 8 a.m. to 4 p.m. CT, Monday through Friday, excluding holidays, and ask for Consumer Relations, or visit the firm’s web site at www.weil-mclain.com.

View Recall

Red square (middle right) highlights affected area.

Red square (middle) shows closer view of affected area.

Close-up of affected screws.

Williamson-Thermoflo – Furnaces & Boilers equipped with Carlin oil burners – CPSC Recall #16-731 (Mar. – 2016)
Description:
This recall includes Williamson and Thermoflo furnaces and boilers with Carlin oil burners with an installation date label between April 1, 2015 and November 31, 2015. The installation date is printed on a label on the outside of the furnace or boiler. Recalled furnaces have a Carlin burner inside of the furnace, behind the furnace grate. Recalled boilers have a Carlin burner attached to the outside of the boiler enclosure. “Carlin” is printed in white letters on the face of the burner nameplate..
View Recall

Williamson-Thermoflo Furnace

Williamson-Thermoflo Furnace

Williamson-Thermoflo Boiler

Williamson-Thermoflo Boiler

Carlin Oil Burner

Carlin Oil Burner

Williamson-Thermoflo – GWS and GWI Boilers – CPSC Recall #08-567 (May – 2008)
Name of Product: Williamson-Thermoflo GWS and GWI Gas Boilers
Units: About 1,800
Manufacturer: Weil-McLain, of Michigan City, Ind.
Hazard: If there is a leak in the vent piping, the recalled boilers can leak carbon monoxide (CO) into the buildings in which they are installed, posing a risk of CO poisoning.
Incidents/Injuries: None reported.
Description: : The recall involves cast iron, gas-fired boilers used for space heating. The following model names and serial numbers are included in the recall.
Model Name Serial Numbers
GWS-127, GWS-158 From CP 5160092 through CP 5663040
GWI-063, GWI-095, GWI-127, GWI-158 From CP 4363986 through CP 5699844
The model name and serial number are located on separate labels on the outside of the left panel.
Sold by: Plumbing and heating wholesale distributors to plumbers and contractors nationwide from October 2001 through December 2007 for between $1,500 and $2,700.
Manufactured in: United States
Remedy: Consumers who have not already been contacted, should contact their installer for a free safety inspection and repair, if necessary.
Consumer Contact: For more information, contact Williamson-Thermoflo toll-free at (866) 783-9516 between 8 a.m. and 4 p.m. CT Monday through Friday, or visit the firm’s Web site at www.williamson-thermoflo.com
View Recall

Williamson-Thermoflo GWS and GSI Gas Boilers

Williamson-Thermoflo GWS and GSI Gas Boilers

York – Packaged Terminal Air Conditioner/Heat Pump (PTAC) units – CPSC Recall #14-263 (Aug. – 2014)
Description:
This recall involves Amana, Century, Comfort-Aire, Goodman and York International-branded Packaged Terminal Air Conditioners and Heat Pumps. The units are rated 230/208 volt, 3.5 kW and are most often installed in walls of hotels, motels, apartment buildings and commercial spaces to provide room climate control. The recalled units are beige with serial numbers ranging from 0701009633 through 0804272329. The brand name is located on the unit’s front cover. The serial number is located on the control board plate found by lifting the unit’s front cover.
View Recall

Amana, Century, Comfort-Aire, Goodman and York International Packaged Terminal Air Conditioner/Heat Pump (PTAC)

Amana, Century, Comfort-Aire, Goodman and York International Packaged Terminal Air Conditioner/Heat Pump (PTAC)